Plant Controller: VAR1

 

Model Equations and/or Block Diagrams

Parameters:

VADJF Voltage adjuster bypass of pulse generator, 0 inactive, 1 active
Tslew Voltage adjuster travel time, sec.
VREFmax Voltage adjuster maximum output, pu
VREFmin Voltage adjuster minimum output, pu
Ton Voltage adjuster pulse generator time on, sec.
Toff Voltage adjuster pulse generator time off, sec.
QREF VAR controller reference setpoint, pu
VITmin VAR controller minimum terminal current limit, pu
VVTmin VAR controller minimum terminal voltage limit, pu
VVTmax VAR controller maximum terminal voltage limit, pu
VVARC_BW VAR controller deadband magnitude, pu
TVARC VAR controller delay time, sec.