Plant Controller: VAR1
Following checks and corrections are applied during Validation and AutoCorrection.
-
If VREFmax < VREFmin then swap the values.
Mult represents the user-specified value Minimum time constant size as multiple of time step option on the Validation page of the Transient Stability Dialog
TimeStep represents the integration time step being used as described on TimeStep
Following treatment is handled during the transient numerical simulation
- If VADJ > VREFmax, then VREFmax = VADJ limits or if VADJ < VREFmin, then VREFmin = VADJ
Model Equations and/or Block Diagrams
Parameters:
| VADJF | Voltage adjuster bypass of pulse generator, 0 inactive, 1 active |
| Tslew | Voltage adjuster travel time, sec. |
| VREFmax | Voltage adjuster maximum output, pu |
| VREFmin | Voltage adjuster minimum output, pu |
| Ton | Voltage adjuster pulse generator time on, sec. |
| Toff | Voltage adjuster pulse generator time off, sec. |
| QREF | VAR controller reference setpoint, pu |
| VITmin | VAR controller minimum terminal current limit, pu |
| VVTmin | VAR controller minimum terminal voltage limit, pu |
| VVTmax | VAR controller maximum terminal voltage limit, pu |
| VVARC_BW | VAR controller deadband magnitude, pu |
| TVARC | VAR controller delay time, sec. |